Type
No |
| |
ELRM44V-30 |
 |
|
| |
ELRM44F-0300 |
 |
|
 |
ELRM44F-0100 |
 |
|
| |
ELRM44F-0030 |
 |
|
|
Description |
Earth Leakage Relay |
Earth Leakage Relay |
Earth Leakage Relay |
Earth Leakage Relay |
|
Function |
Variable - Type A (True R.M.S.) |
Variable - Type A (True R.M.S.) |
Variable - Type A (True R.M.S.) |
Variable - Type A (True R.M.S.) |
|
Supply
voltage Un |
12 - 125V DC, 24, 115/230V, 400VAC 50/60Hz
|
12 - 125V DC, 24, 115/230V, 400VAC 50/60Hz
|
12 - 125V DC, 24, 115/230V, 400VAC 50/60Hz
|
12 - 125V DC, 24, 115/230V, 400VAC 50/60Hz
|
|
Sensitivity IDn |
30, 100, 300, 500mA, 1, 3, 5, 10, 20, 30A (selectable) |
300mA |
100mA |
30mA |
|
Range |
0 - 30A |
- |
- |
- |
|
Time
delay |
inst., 0.06, 0.15, 0.25, 0.5, 0.8, 1, 2.5, 5, 10sec.
(selectable) |
inst. (<25mS when fault current @ 5 x IDn) |
inst. (<25mS when fault current @ 5 x IDn) |
inst. (<25mS when fault current @ 5 x IDn) |
|
LED
indication |
Power On indication (Green) |
Power On indication (Green) |
Power On indication (Green) |
Power On indication (Green) |
| |
Tripped indication (Red) - LED flashes during toroid
open circuit |
Tripped indication (Red) - LED flashes during toroid
open circuit |
Tripped indication (Red) - LED flashes during toroid
open circuit |
Tripped indication (Red) - LED flashes during toroid
open circuit |
| |
LED Bargraph showing leakage current (25, 50 and 75%
of IDn) |
- |
- |
- |
|
Test/Reset facility |
Local and Remote |
Local and Remote |
Local and Remote |
Local and Remote |
|
Output |
1 x SPDT (S.O.)/ 1 x SPNO (P.S.O.) |
1 x SPDT (S.O.) |
1 x SPDT (S.O.) |
1 x SPDT (S.O.) |
|
Output
rating |
8A @ 250VAC (AC1) - S.O. 6A @ 250V AC (AC1) - P.S.O. |
8A @ 250VAC (AC1) |
8A @ 250VAC (AC1) |
8A @ 250VAC (AC1) |
|
50%
Fault level output |
- |
- |
- |
- |
|
Adjustment cover and tamperproof seal |
Yes |
No |
No |
No |
|
Ratio |
- |
- |
- |
- |
|
Internal Dimension |
- |
- |
- |
- |
|
External Dimensions in mm |
- |
- |
- |
- |